Cert. No. British Standard Test Date Description
7963 BS4070:1966 Jun-75 Modular Control Board Busbar System 1600A
45kA, 3s. 112kA peak (Bars = 2/ph & I/N)
8769 BS5486:Part 1:1977
IEC 439:1973
Aug-80 1600A FBA Busbar System
71kA, 1s. 156kA peak
8773 BS5486:Part 1:1977
IEC 439:1973
Aug-80 800A FBA Busbar System
50kA, 1s. 105kA peak
8785 BS5486:Part 1:1977
IEC 439:1973
Sep-80 1600A FBA Busbar System
50kA, 3s. 112kA peak
9132 BS5227:1975
Clause 26
Dec-81 12kV- Busbar Trunking
3 – 101.2 x 6.35mm, 50kA, 3s. 125kA peak
28kV, 1min power frequency withstand voltage
9133 BS5486:Part 1:1977 Dec-81 FBA Busbar System 3000A and 2500A and 630A Starter
50kA, 3s. 105kA peak (Bar = 3/Ph & 2/N)
9802 BS5486:Part 1:1977 May-84 Supplementary cert. to 8773, for outgoing circuits.
9858 BS4941: Part 1:1979 App C, Clause 6. Feb-84 Starter co-ordination type “C”
11440 BS5486:Part 1:1986
IEC439-1:1985
Jun-90 FBA Busbar System
51mm x 6.35mm – 50kA, 1s. 105kA peak
25.4mm x 6.35mm – 25kA, 1s. 52.5kA peak
11463 BS5486:Part 1:1986
IEC439-1:1985
Jun-90 FBA Busbar System – 80kA, 1s. 176kA peak
2 x 76 x 6.35mm
12744 BS EN 60439-1:1994
IEC 439-1:1992
Jun-95 FBA Busbar System – 80 kA, 1s. 176kA peak
2 x 152.4mm x 6.35mm
12745 BS EN 60439-2:1993
IEC 439-1:1992
May-95 Busbar Trunking – 80 kA, 1s. 176kA peak
2 x 152.4mm x 6.35mm
Test Report 1668 BS 159:1992 Feb-96 Cable link box.
16kA, 1s. 40kA peak
28kV, 1 min power frequency withstand voltage
75kV lightning impulse withstand test
12915 BS EN 60439-1:1994
IEC 439-1:1992
Mar-96 FBA Busbar System – 50kA, 1s. 105kA peak
3 x 101.6mm x 6.35 mm
3 x 76.2mm x 6.35 mm
2 x 76.2mm x 6.35 mm
1 x 50.8mm x 6.35 mm
12928 BS EN 60439-1:1994
IEC 439-1:1992
Apr-96 FBA Busbar System – 80 kA, 1s. 176kA peak
3 x 152.4mm x 6.35mm
Report of Performance
No.6328-0
Apr-96 Prospective rated internal fault arcing current
80 kA, 0.1s. 176kA peak
14439 BS EN 60439-1:1999 Feb-00 50 kA, 1s, 105 kA peak,
1 – 50 x 6mm Vertical Busbar,
1 – 50 x 6 mm Horizontal Busbar,
1 – 100 x 6mm Horizontal Busbar.
1 – 50 x 6mm ACB Connections and ISOVAL TM support straps.
14482 BS EN 60439-1:1999 May-00 50 kA, 1s, 105 kA peak,
1 – 50 x 10mm Horizontal Busbar,
1 – 50 x 6mm Vertical Busbar,
1 – 160 x 10mm Horizontal Busbar,
1 – 50 x 10mm ACB Connections, Vertical Busbars & incoming palms.
80kA, 1s. 176 kA peak,
2 x 100 x 10mm horizontal Busbars.
14487 BS EN 60439-1 :1999 Sep-00 1 – 100 x 6mm
50 kA, 1s. 105kA Peak, 3 Ph.
30 kA, 1s. 63 kA Peak Ph-N.
1 – 100 x 6mm HDHC. 30 kA, 1s. 63 kA peak P-E.
2 x 50.8 x 6.35mm, 48kA, 1s 100.8kA peak P-E.
14904 BS EN 60439-1 :1999 May-01 100 kA, 1s. 230kA Peak, 3 Ph. 60 kA, 1s. 132 kA Ph-N / Ph-E.
2 x 200 x 10mm Horizontal Busbar.
1 x 120 x 10mm Feeder Vertical Busbar.
3 x 100 x 10mm ACB Connections.
3.5kV dielectric test.
14905 BS EN 60439-1 :1999 May-01 2 x 160 x 10mm Main Busbar & 4000A 4P ACB through fault.
80kA, 1s. 200 kA Peak, 3 Ph.
60 kA, 1s, 132kA Peak Ph-N / Ph-E.
Conditional SC test on Fuse & Fuse switches -
32A, 63A, 100A, 200A, 400A @ 50kA.
XZ 232 F 01 IEC 60298, 3rd Ed 1990-12 Apr-02 5 x 10mm main busbars @ 33.4kA, 3s, 82.9kA peak
Earth switch @ 25.9kA, 1s, 64.5kA peak.
XZ 232 F 02 IEC 60298, 3rd Ed 1990-12 Apr-02 VCB & cable box @ 31.5kA, 3s, 84kA peak
Earth Switch @ 41.6kA, 1s, 104kA peak
5 x 10mm VCR riser @ 51.1kA, 1s, 127kA peak
100 x 10mm busbars @ 52.2kA, 3s, 127kA peak
XZ 232 L02 IEC 60298, 3rd Ed 1990-12 Apr-02 4 panel MV switchboard
Arc fault containment to Annex AA, 25kA, 1s
TZ 185 Z 01 IEC60290, 3rd Ed 1990-12
IEC60694, Ed2.2, 2002-01
Apr-02 4 panel MV switchboard
75kV lighting impulse withstand tests
28kV power frequency withstand voltage
TZ 185 02 IEC60290, 3rd Ed 1990-12
IEC60694, Ed2.2, 2002-01
Apr-02 CT bushing insulation
75kV lightning impulse withstand tests
28kV power frequency withstand voltage
TZ 185 Z 03 Shell DEP Apr-02 1-hour power frequency withstand voltage test of standard busbar insulation.
1hr @ 11kV then 1hr @13.8kV then 1hr @17Kv. (= 3 hr test)
SD200407-001 BS EN 60529:1992 Jul-06 IP5X – Probe and Dust ingress
Para 13.4, 13.5, Dust category 1
SD200407-002 BS EN 60529:1992 Jul-06 IPX4 – Water ingress
Para 14.2.4(b), fig 5 nozzle – spray
16705 BS EN 60439-1:1999 Oct-07 2 x 100 x 10mm Main Busbar & 3200A 4P ACB through fault.
80kA, 1s. 176kA peak, 3Ph.
48kA, 1s. 101kA peak, Ph-N.
1 x 50 x 10mm Main Earth Bar
48kA, 1s. 101kA peak, Ph-E.
16706 BS EN 60439-1:1999 Oct-07 1 x 50.8 x 6.35mm Main Busbar & 800A 4P ACB through fault.
50kA, 1s, 105kA peak, 3Ph.
30kA, 1s, 63kA peak, Ph-N.
1 x 50.8 x 6.35mm Main Earth Bar.
30kA, 1s, 63kA peak, Ph-N.
Conditional SC test @ 415V, 3Ph, 50kA, 105kA peak, Pf = 0.25 800A 4P, ACB (fault make test – open routine).
11kW, 30kW, 55kW Intelligent DOL Starters (fuselink rupture).
160A, 250A, 400A MCCBs (MCCB fault trip routine).
TEA002490CC01A BS EN 61439-1:2009
Clause 10.2.2.4 – Severity A
Apr-11 Resistance to corrosion – Complies with ISO 4628-3 degree of rusting Ril, Seals not damaged, Mechanical Integrity not impaired, doors, hinges, locks and fastenings work without abnormal effort.
20555 BS EN 61439-2:Ed 2.0
2011-08
Feb-15 Clause 10.5 – protection agaist electric shock in itegrity of PE cct
Earth bar = 1-50x10mm HDHC bare
Icw: 48kA rms, 1s,       Ipk: 100.8kA peak,     single phase
Clause 10.11 – short cct withstand strength
Horizontal = 2/1-100x10mm, Vertical = 1-60x10mm HDHC, bare
Icw: 80kA rms, 1s,       Ipk:176kA peak,         3 phase,
Icw: 48kA rms, 1s,       Ipk: 100.8kA peak,     single phase
Outgoing Circuit – ABB EMAX 2 3200A ACB, 4/2-100x10mm HDHC
Icw: 80kA rms, 1s,       Ipk:176kA peak,         3 phase,
Icw: 48kA rms, 1s,       Ipk: 100.8kA peak,     single phase
20556 BS EN 61439-2:Ed 2.0
2011-08
Feb-15 Clause 10.5 – protection agaist electric shock in itegrity of PE cct
Earth bar = 1-50x10mm HDHC bare
Icw: 48kA rms, 1s,        Ipk: 100.8kA peak,      single phase
Clause 10.9 – Dielectric properties
Clause 10.9.2 – Power Frequency
Ue: = 400V,        Ui: = 1000V,      2200V rms, 5s
Clause 10.11 – short cct withstand strength
Horizontal = 2/1-60x10mm, Vertical = 1-60x10mm HDHC, bare
Icw: 50kA rms, 1s,        Ipk: 105kA peak,        3 phase,
Icw: 30kA rms, 1s,        Ipk: 63kA peak,          single phase
Outgoing Circuit – ABB EMAX 2 2000A ACB, 2/1-60x10mm HDHC
Icw: 50kA rms, 1s,        Ipk: 105kA peak,        3 phase,
Icw: 30kA rms, 1s,        Ipk: 63kA peak,          single phase

Note: FBA = Factory Built Assembly